Type Tests

TYPE TESTS

We have Type Tested our Panel at CPRI for Short Circuit, Temperature Rise, and IP 54 & IP 55 Degree of Protection for enclosure. Find below the list of Type Tests undergone in CPRI.
Our panel boards are Type Tested as per IEC 61439 – 1 & 2 (Latest Edition) at CPRI.

CPRI Tested

IEC 61439 - 1 & 2

Short Circuit Tested

Temperature Rise Tested

IP 54 & IP 55 Protection

Type Tested at CPRI

We have Type Tested our Panel at CPRI for Short Circuit, Temperature Rise, and IP 54 & IP 55 Degree of Protection for enclosure. Find below the list of Type Tests undergone in CPRI.
Our panel boards are Type Tested as per IEC 61439 – 1 & 2 (Latest Edition) at CPRI.

CPRI Type Tested Panel Boards

Short Circuit Temperature Rise IP 54 and IP 55 Degree of Protection for enclosure as per the Type Tests undergone in CPRI

TYPE TEST OVERVIEW

Internal Arc Withstand Test

4000Amps
65kA rms for 0.3 seconds
IEC TR 61641 Edition 3.0 : 2014

Complete Verification Tests

2500Amps and 3200Amps LT Panel
ABB and Schneider Switchgear Components
IEC 61439-1:2011 & IEC 61439-2:2011

Temperature Rise Tests

5000Amps and 3200Amps
LT Panel and LT Bus duct
IS 8623 / IEC 60439

Short Circuit and IP Protection Tests

65kA rms and 50kA rms
IP 55 Outdoor and IP 54 Indoor
IS 8623 / IS IEC 61439 / IS 13947

Type Tests undergone in CPRI

2500Amps LT Panel

Type Test of complete verfication tests for 2500Amps on LT Panel
M/s. Schneider Switchgear Components

Complete Verification Tests in accordance with Standard / Specification as per:
IEC 61439-1:2011 & IEC 61439-2:2011

Sub-clause Nos.:
10.10.2, 10.2.3.1, 10.9, 10.4, 10.11, 10.5, 10.2.6, 10.13, 10.2.7, 10.2.5, 10.2.3.3, 10.3, 10.2.2 & 10.12


3200Amps LT Panel

Type Test of complete verfication tests for 3200Amps on LT Panel
M/s. Schneider Switchgear Components

Complete Verification Tests in accordance with Standard / Specification as per:
IEC 61439-1:2011 & IEC 61439-2:2011

Sub-clause Nos.:
10.10.2, 10.2.3.1, 10.9, 10.4, 10.11, 10.5, 10.2.6, 10.13, 10.2.7, 10.2.5, 10.2.3.3, 10.3, 10.2.2 & 10.12

2500Amps LT Panel

Type Test of complete verfication tests for 2500Amps on LT Panel
M/s. ABB Switchgear Components

Complete Verification Tests in accordance with Standard / Specification as per:
IEC 61439-1:2011 & IEC 61439-2:2011

Sub-clause Nos.:
10.10.2, 10.2.3.1, 10.9, 10.4, 10.11, 10.5, 10.2.6, 10.13, 10.2.7, 10.2.5, 10.2.3.3, 10.3, 10.2.2 & 10.12


3200Amps LT Panel

Type Test of complete verfication tests for 3200Amps on LT Panel
M/s. ABB Switchgear Components

Complete Verification Tests in accordance with Standard / Specification as per:
IEC 61439-1:2011 & IEC 61439-2:2011

Sub-clause Nos.:
10.10.2, 10.2.3.1, 10.9, 10.4, 10.11, 10.5, 10.2.6, 10.13, 10.2.7, 10.2.5, 10.2.3.3, 10.3, 10.2.2 & 10.12

Temperature Rise Test for 5000Amps

Temperature Rise Test for 5000Amps on bus bars for LT Panel

Test in accordance with Standard / Specification stipulated in:
IS 8623 (Part 1) : 1993 / IEC Pub 60439 – 1 (1985) (RA-2008)


Temperature Rise Test for 3200Amps on LT Panel

Temperature Rise Test for 3200Amps on bus bars for LT Panel

Test in accordance with Standard / Specification stipulated in:
IS 8623 (Part 1) : 1993 / IEC Pub 60439 – 1 (1985)


Temperature Rise Test for 3200Amps on LT Bus duct

Temperature Rise Test for 3200Amps on Bus bars for LT Bus duct

Test in accordance with Standard / Specification stipulated:
IS 8623 (Part 2) : 1993 / IEC 60439 – Part – 2 – 1987 (RU-2008)

Verification of Internal Arc withstand test:
4000Amps, 65kA rms for 0.3 seconds

Test in accordance with Standard/Specification as per:
IEC TR 61641 Edition 3.0 : 2014

LT Panel 65kA rms

Verification of Short Circuit withstand strength:
65 kA rms for 1 Second & 143kA Peak on bus bars for LT Panel

Test in accordance with Standard / Specification stipulated in:
Sub-clause 8.2.3 of IS 8623 (Part 1) : 1993 / IEC Pub 439 – 1 (1985)


LT Bus duct 65kA rms

Verification of Short Circuit withstand strength:
65 kA rms for 1 Second & 143kA Peak on bus bars for LT Bus duct

Test in accordance with Standard / Specification stipulated in:
Sub-clause 8.2.3 of IS 8623 (Part 2) : 1993 / IEC Pub 439 – 2 (1987)


LT Panel 50kA rms

Verification of Short Circuit withstand strength:
50 kA rms for 1 Second & 105kA Peak on bus bars for LT Panel

Test in accordance with Standard / Specification stipulated in:
Sub-clause 8.2.3 of IS 8623 (Part 1) : 1993 / IEC Pub 439 – 1 (1985)

IP 55 Degree of Protection Test Outdoor

Degree of Ingress Protection IP 55 Test Outdoor for LT Panel

Test in accordance with Standard / Specification stipulated in:
IS/IEC61439-1 Edition 1.0, 2009-01 Standard Test of IS/IEC 60529 Edition 2.1, 2001-02 Standard Clause 13.4


IP 54 Degree of Protection Test Indoor

Degree of Ingress Protection IP 54 Test Indoor for LT Panel

Test in accordance with Standard / Specification stipulated in:
IS 13947 (Part 1) : 1993 (reaffirmed 2004)

VERIFIED FOR PERFORMANCE AND SAFETY

Our testing process supports reliable panel performance by verifying critical electrical and mechanical parameters before delivery Each panel is checked as per project requirements approved drawings and applicable inspection procedures

TUV India ISO 9001 2015 Certificate

CPRI Type Test Certificate Complete Verification Tests

CPRI Type Test Certificate Complete Verification Tests

CPRI Complete Verification Testing Certificate

Internal Arc withstand Test - ERDA

CPRI Test Report Temperature Rise 4000A LT Panel CPRIBLRSCL23T0657

CPRI Test Report Short Circuit Withstand Strength 4000A LT Panel CPRIBLRSCL23T0671

Give us a call

Available from 10:00 am to 5:30pm, Monday to Friday.

Send Us Your Requirment

Submit your project details

Our usual reply time: 1 Business day